Metal-Enclosed (Air Insulated / Secondary)

In an electricity distribution grid, Metal-Enclosed Switchgears are factory assembled, metal enclosed set of switchgear used at the load connection points of either ring-type or radial distribution networks. It has many different options of functional units; namely transformer protection units (with fıse or circuit breaker -SF6 or Vacuum), metering unit, coupling unit, etc.
Air Insulated Metal-Enclosed Switchgears can be characterized by their type of insulation which is air. The switch used to isolate the transformer can be a fusible switch, or may be a circuit breaker using vacuum or gas-insulated interrupters. The unit may also include protective relays to operate the circuit breaker on a fault.
Rated Voltage | kV | 12 … 40,5 kV |
Frequency | Hz | 50/60 |
Rated Power Frequency Withstand Voltage | kV | 10 … 85 kV |
Rated Lightning Impulse Withstand Voltage | kV | 40 … 185 kV |
Short-Circuit Breaking Current | kA | 16 … 25 |
Short-Time Withstand Current, 1/3s | kA | 16 … 25 |
Rated Current | A | 200 … 1250 |